How to deal with the trouble of regulating valve in use?
Nov 08, 2019
I. the regulating valve does not operate
● 1 reason: there is no air source or the air source pressure is too small.
Measures: firstly, check whether the air source (instrument air) is unobstructed and whether the air source pressure meets the use requirements of the valve.
● 2 reason: there is air source and no output signal pressure.
Measure 1: for electric control intelligent regulating valve, check the power supply of control signal line of Valve Intelligent positioner, use digital multimeter to measure whether the control power signal dc4-20ma in central control room is normal, if not, check PLC system, line and other faults, if normal, replace the valve positioner.
Measure 2: for the mechanical controller or positioner, the mechanical pressure controller or positioner shall be replaced.
Measure 3: for the control valve of the mechanical controller, check whether the signal collection pipeline valve of the medium on the installation pipeline of the control valve is fully open or seriously leaking. If there is any abnormality, handle it in time.
● 3 reason: the output signal air pressure is normal and still does not act.
Measure 1: check whether the diaphragm of pneumatic diaphragm actuator has serious air leakage. If there is air leakage, replace the diaphragm and relevant seals in time.
Measure 2: if the diaphragm is in good condition without air leakage, the main valve core, bushing and valve seat shall be stuck, the main valve shall be disassembled and inspected, and sundries shall be removed.
Measure 3: the valve rod is seriously bent and deformed, and the main valve shall be disassembled and inspected, and replaced according to the inspection results.
Measure 4: if there is leakage in the signal air supply pipeline, check and handle the leakage point.
Measure 5: if the signal amplifier fails or is improperly adjusted, and the main air source does not enter the diaphragm chamber through the amplifier, adjust or replace the amplifier in time.
II. Slow action of regulating valve
● 1 cause: the valve body is blocked by slime.
Measures: disassemble the main valve body and clean the stickiness in the valve body.
● 2 reasons: the valve stem packing is deteriorated and hardened or the graphite and asbestos packing lubricating oil is dry.
Measures: disassemble the main valve body and replace the stem packing.
● 3 reasons: too tight packing, increased friction resistance.
Measure 1: after loosening the gland nut of stem packing, reciprocating the main valve several times, and adjust the gland nut of stem packing to the proper torque.
Measure 2: if measure 1 has no effect, replace the stem packing and adjust the stem packing compression nut to the appropriate torque.
● 4 reasons: the stem is not straight, resulting in high friction resistance.
Measures: disassemble the main valve and replace the valve rod.
● 5 cause: there is slight air leakage in diaphragm or signal air pipeline of pneumatic diaphragm actuator.
Measures: replace the diaphragm of the pneumatic diaphragm actuator, and deal with the air leakage in the signal gas pipeline.